Rheem AC Troubleshooting. Disconnect all power to unit before servicing. Contactor may break only one side. Failure to shut off power can cause electrical shock resulting in personal injury or death. If you're looking for help fixing your Rheem Furnace, look no further! Our comprehensive Rheem Furnace error code guide will explain common issues, provide tips,.
- POST a QUESTION or COMMENT Noritz water heaters, error codes, manuals, installation, repairs
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
Noritz tankless gas water heater manuals, error codes, * company contact information.
We give contact information for Noritz water heater, geyser, cylinder, calorifier manufacturers and for water heater installation, operation, & troubleshooting manuals.
Our photo at page top shows a Noritz tankless water heater. Noritz heaters are available in models for either natural gas or propane.
We also provide a MASTER INDEX to this topic, or you can try the page top or bottom SEARCH BOX as a quick way to find information you need.
Noritz Tankless Water Heater Age, Manuals, Error Codes
Noritz Tankless Water Heater Standard Error Codes
Watch out: your water heater model may use different codes or may provide error codes that are not given here. Therefore you'll want to consult the manual for your specific heater.
Table of Noritz Tankless Water Heater Error Codes | |
Error Code | Meaning |
10 | Problem in gas combustion that causes the power level drop, while the combustion continues even after shutdown. Check for foreign materials found on the burner which is burning after gas combustion stops. To reset the error code 10, the power must be disconnected. If there is a recirculation loop use an aquastat to keep 10 degree differential. |
11 | Ignition Failure. Check that the gas valve oopens. Press power button to turn unit off, open a hot water faucet, turn unit back on. If the error code no longer flashes the problem is solved. Check for proper gas type (LP vs Natural gas), pressure, free flow through gas piping and valves, clean flame rod, no blockage in vent or vent connector, clean ignition plug. See Noritz Tankless Water Heater Seven Common Error Codes & Repairs [PDF] |
12 | Burner flame loss during operation, or Bad flame detection rod. Check for proper gas pressure, free flow, no blockage in vent. Clean ignitionplug & flame sensor rod. See Noritz Tankless Water Heater Seven Common Error Codes & Repairs [PDF] |
14 | Thermal fuse failure. Replace the thermal fuse. The thermal fuse is a white cord which wraps around the heat exchanger. Failure cause: scaled or dirty heat exchanger, Check for obstructed combustion air flow, clean proper burner operation. Check water quality for hardness or sediment that can clog the heat exchanger. Flush scaled heat exchanger. |
16 | Extremely high water temperature. Watch out: dangerous scalding hazard. See Noritz Tankless Water Heater Error Code 16 [PDF] See also Noritz Tankless Water Heater Seven Common Error Codes & Repairs [PDF] Check for sediment or scale clogging and clean or de-scale the unit using a cleaner such as vinegar or a de-scaler. Check manifold pressure adjustment. |
20 | High limit switch activated. Check or replace high limit switch. Check for scale and de-scale the heater. |
29 | High water level in neutralizer; neutralizer clogged. Check for clogged condensate drain; check for damp or wet or damaged water level sensor. Check for frozen neutralizer due to condensate clogging. See Noritz Tankless Water Heater Seven Common Error Codes & Repairs [PDF] |
31 | Inlet thermistor failure. Replace the inlet thermistor. |
32 | Outlet thermistor failure. Replace the outlet thermistor. |
33 | Heat exchanger thermistor failure. Replace the thermistor. |
43 | Invalid number, possibly mis-read for actual code 73. |
51 | Noritz Code 51: Gas Manifold Solenoid Failure A reader opined that for some models this code means Noritz manifold replacement is needed. See Error Code 59 below. |
59 | Low input BTU, insufficient gas supply, combustion problems such as obstructed exhaust flow. Check for adequate combustion air; check for blocked exhaust venting; clean fan motor & burner chamber. Check for a stuck exhaust damper or too-long or too many elbows in exhaust vent. Check that the heater is properly set for the elevation where installed. Occurs if natural gas pressure is below 5' WC or propane below 8' WC. |
61 | Fan motor failure. Check voltage to the fan motor. Replace faulty fan motor or faulty circuit board (that controls the fan). |
65 | Main flow control valve abnormality Check for blockage of main servo |
66 | Bypass flow control valve failure. Check for blockage of the bypass servo valve or replace the valve. |
70 | Circuit board fault. |
71 | Gas valve drive circuit abnormality. Water heater connected to battery backup, solar power, or generator and voltage supply is not stable. Check voltage delivered from circuit board. In area of unstable power, install a power surge protector. |
72 | Flame rod flame detection error: flame detected without proper ignition sequence. Check for proper electrical ground. Check for damaged circuit board. Check for damaged flame detection circuit / wires. |
73 | Circuit board setting error. Re-set the unit by disconnecting power. Review & correct circuit board programming / switches. Common cause: connection changed with power on. If failure persists replace the circuit board. See Noritz Tankless Water Heater Seven Common Error Codes & Repairs [PDF] |
F76 | Multi-system communication error. Disconnect power to reset the unit. Check cord connections. See Noritz Tankless Water Heater Seven Common Error Codes & Repairs [PDF] |
760 | Remote controller problem. Re-set the unit. Check for loose wire connections. Check that only 1 remote controller is connected to the heater. |
90 / 99 | Combustion gas alert. Check for proper gas flame color (light blue, yellow tips). Check for blocked flue, dirt on gas burner. Have a professional check the gas supply pressure. |
99 | Contact Noritz |
F90 | Comnbustion gas alert. Have a professional check the gas supply pressure. |
F99 | See Noritz Tankless Water Heater Seven Common Error Codes & Repairs [PDF] |
92 / 93 F92 | Neutralizer life cycle alert. Replace the neutralizer & re-set the burner timer. |
Other error codes not in this table: Contact Nortiz. |
How to use this Noritz water heater error code table
Sources: Noritz Water Heaters, Noritz North America Headquarters: 11160 Grace Avenue Fountain Valley, CA 92708 Phone: 714-433-2905
Watch out: some water heater defects represent dangerous conditions, risking fire, explosion, or carbon monoxide poisoning or scalding hazards. Work on these heaters must be by a qualifed service professional.
See the water heater manual or troubleshooting manual for your specific water heater model for expanded detail about the meaning and the corrective steps for each of these error codes.
Noritz Water Heater Manual Free Downloads
Image: the Noritz CB180 combination boiler, whole house dmoestic water heater, 18,000 to 180,000 BTUh and 0.5 to 9.1 GPM.
- Contact Noritz Water Heaters, Noritz North America Headquarters: 11160 Grace Avenue Fountain Valley, CA 92708 Phone: 714-433-2905
Noritz Atlanta, 1220 Kennestone Circle, Suite 126 Marietta, GA 30066 Phone: 770-422-8120
Noritz Canada: Email: sales@noritz.com
If at any time during the installation and setup of a Noritz product you have questions or concerns, contact Noritz America Engineering & Service
at 866-766-7489 or
http://support.noritz.com/. - NORTIZ NCC199(-SV, -DV), NRC111(-SV, -DV) Error Code Lists with Remote [PDF] retrieved 2018/10/14, original source: http://support.noritz.com/assets/error_code_list.pdf
- NORITZ NR71-SV, NR71-OD TANKLESS GAS WATER HEATER NR-series [PDF] Models : NR71-SV, NR71-OD* (For USA and Canada) and NR66-SV, NR66-OD* (For USA and Canada) and NR50-OD* (For USA only)
- NORITZ NRCP1112-DV / NRCP982-DV CONDENSING TANKLESS GAS WATER HEATER INSTALLATION MANUAL [PDF] Models NRCP1112-DV / NRCP982-DV (Eco TOUGH)
- NORITZ NRCP1112-DV / NRCP982-DV (CONDENSING GAS TANKLESS WATER HEATER MANUAL Eco TOUGH) [PDF] NG / LP
- NORITZ NRCP1112-DV / TANKLESS WATER HEATER MANUAL NRCP982-DV (Eco TOUGH) [PDF]
- NORITZ NRC98-DV NRC98-OD NRC83-DV NRC83-OD CONDENSING TANKLESS GAS WATER HEATER OWNER'S GUIDE [PDF] (2013) Models: NRC98-DV NRC98-OD NRC83-DV NRC83-OD,
- NORITZ NRC111DV CONDENSING TANKLESS GAS WATER HEATER GUIDE NRC111 series [PDF] Models : NRC111DV (GQ-C3257WX-FF US) NRC111OD (GQ-C3257WX US)
- NORITZ NRC711-OD CONDENSING TANKLESS GAS WATER HEATER MANUAL & NRC661A-OD [PDF] Outdoor Installation manual, retrieved 2018/10/14 original source: https://www.noritz.com/media-archive/NRC711_OD_installationmanual.pdf
- NORITZ NCC1991-ODCONDENSING TANKLESS GAS WATER HEATER [PDF] retrieved 2018/10/14 original source: https://support.noritz.com/download.php?file=Literature Page/Installation Manual/NCC1991O IM.pdf&field=InstallationManual
- NORITZ N-084M TANKLESS WATER HEATER MANUAL Model [PDF] (2005)
- NORITZ NRC663-FSV TANKLESS WATER HEATER MANUAL Model (EZTR40) [PDF] (2014) sold by Home Depot & other suppliers.
- NORITZ SYSTEM CONTROLLER MANUAL SC-301-6M [PDF] (2012)
- Noritz Tankless Water Heater Error Code 16 [PDF] [unsafe temperature] retrieved 2018/03/19, original source: http://www.noritz.com/wp-content/ uploads/16-Error-code.pdf
- Noritz Tankless Water Heater Seven Common Error Codes & Repairs [PDF], retrieved 2018/03/19, original source: http://www.noritz.com /blog/ how-to-resolve-the-seven-most-common-noritz-tankless-error-codes/
- Noritz Tankless Water Heater ERROR CODES & TROUBLESHOOTING GUIDE (2017), Noritz Tankless Water Heaters
Reader Comments & Q&A
On 2020-01-07 by Anonymous
Noritz water heater Error code 90
On 2019-03-28 - by (mod) -
Manuel
Either there is a leak and hot water is actually running somewhere or your water heater's control is faulty and UNSAFE.
Watch out: I would TURN OFF the system IMMEDIATELY and call for help from a licensed plumber who is familiar with Noritz water heaters.
Rheem Furnace Fault Codes
On 2019-03-21 by Manuel
Water heater runs constantly, not just when using hot water. Water seems very hot
On 2019-01-28 - by (mod) -
Earl:
Noritz water heater error codes are displayed:
On Noritz water heater models that contain a display window, the error code appears in that window.
On Noritz water heater models that do not include a display window, the error code can appear on the remote control unit such as the two Noritz water heater remote controllers shown below, the Noritz RC-7651-M and the Noritz remote control
On 2019-01-15 by earl
where are the error codes shown on noritz gas water heater?
On 2018-12-27 16:05:07.250940 - by (mod) -
thanks for the (unnecessarily impolite) comment, Anonymous.
The Noritz manuals we have at hand don't list error code 51 or we'd have included it.
Perhaps you can help us out by giving the Noritz water heater model and age for the unit whose manual lists error code 51 as 'replace manifold'.
InspectApedia.com is an independent free public website having no conflicts of interest, no connection with the sale of any product or service, and dedicated to accurate, unbiased information. Working TOGETHER makes us smarter.
On 2018-12-26 2 by Anonymous - Noritz error code 51 is a real code: Noritz needs a new mainfold
dount know what u r talking about 51 is a real coad called nortz needs manfold
On 2018-10-14 - by (mod) -
I would sure like to see a photo of the data tag on that water heater. I haven't been able to find a Noritz nv83 of any persuasion whatsoever. I'm continuing to look.
On 2018-10-13 by Anonymous
NV83-DVR
On 2018-10-13 - by (mod) - Noritz Error Code 51 - gas manifold solenoid failure
Anon
As in the table above I suspect this code might be model-specific such as the Noritz Model NRC 98-OD.
On some Noritz models error Code 51: Gas Manifold Solenoid Failure
Please take a look at the data tag on your heater, attach a sharp photo of it as an image you can add to a comment, or just tell me the model number and I will dig into this further.
On 2018-10-12 by Anonymous
What is the problem when error code is 51 blinking
...
Continue reading at WATER HEATER LIFE or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
Water Heater Articles
- WATER HEATER AGE DECODING GUIDES - six methods for figuring out the age of a water heater
- WATER HEATER AGE & MANUALS - home
Suggested citation for this web page
NORITZ WATER HEATER ERROR CODES & MANUALS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
INDEX to RELATED ARTICLES: ARTICLE INDEX to WATER HEATERS
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
...
Ask a Question or Search InspectApedia
Questions & answers or comments about how to find out the age of a heating appliance: water heater, heating boiler, heating furnace.
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed:if your comment contains an image, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Technical Reviewers & References
- Scott C. LeMarr has provided his file of keys to decode Water Heater Age from the data provided on the manufacturer's equipment labels. Mr. LeMarr is a professional home inspector, Certified Professional Inspector/President, MASTER Indoor Environmental Specialist (MIES). Vice President of Wisconsin NACHI. He and his company, Honest Home Inspections [ Website: www.HonestHomeInspections.com ], LLC. can be reached at 262-424-5587 or by email to scott@honesthomeinspections.com
- Carson Dunlop, Associates, Toronto, have provided us with (and we recommend)Carson Dunlop Weldon & Associates'Technical Reference Guide to manufacturer's model and serial number information for heating and cooling equipment ($69.00 U.S.). Technical Reference Guide, Carson Dunlop Weldon & Associates, Ltd., 120 Carlton St. Suite 407, Toronto, Ontario, M5A 4K2 Canada, ISBN 1-895585-90-2 165pp.
Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair
- Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
- Carbon Monoxide Gas Toxicity, exposure limits, poisoning symptoms, and inspecting buildings for CO hazards
- ...
- Carson, Dunlop & Associates Ltd., 120 Carlton Street Suite 407, Toronto ON M5A 4K2. Tel: (416) 964-9415 1-800-268-7070 Email: info@carsondunlop.com. The firm provides professional HOME INSPECTION SERVICES and also extensive HOME INSPECTION EDUCATION and home inspection-related PUBLICATIONS. Alan Carson is a past president of ASHI, the American Society of Home Inspectors.
Thanks to Alan Carson and Bob Dunlop, for permission for InspectAPedia to use text excerpts from The Home Reference Book & illustrations from The Illustrated Home. Carson Dunlop Associates' provides extensive home inspection education and report writing material.
The ILLUSTRATED HOME illustrates construction details and building components, a reference for owners & inspectors.
Special Offer: For a 5% discount on any number of copies of the Illustrated Home purchased as a single order Enter INSPECTAILL in the order payment page 'Promo/Redemption' space.
TECHNICAL REFERENCE GUIDE to manufacturer's model and serial number information for heating and cooling equipment, useful for determining the age of heating boilers, furnaces, water heaters is provided by Carson Dunlop Weldon & Associates
Special Offer: Carson Dunlop Associates offers InspectAPedia readers in the U.S.A. a 5% discount on any number of copies of the Technical Reference Guide purchased as a single order. Just enter INSPECTATRG in the order payment page 'Promo/Redemption' space. - The HOME REFERENCE BOOK - the Encyclopedia of Homes, Carson Dunlop & Associates, Toronto, Ontario, 25th Ed., 2012, is a bound volume of more than 450 illustrated pages that assist home inspectors and home owners in the inspection and detection of problems on buildings. The text is intended as a reference guide to help building owners operate and maintain their home effectively. Field inspection worksheets are included at the back of the volume.
Special Offer: For a 10% discount on any number of copies of the Home Reference Book purchased as a single order. Enter INSPECTAHRB in the order payment page 'Promo/Redemption' space. InspectAPedia.com editor Daniel Friedman is a contributing author.
Or choose the The HOME REFERENCE eBook for PCs, Macs, Kindle, iPad, iPhone, or Android Smart Phones.
Special Offer: For a 5% discount on any number of copies of the Home Reference eBook purchased as a single order. Enter INSPECTAEHRB in the order payment page 'Promo/Redemption' space. - Building inspection education & report writing systems from Carson, Dunlop & Associates Ltd
COMMERCIAL BUILDING INSPECTION COURSES - protocol ASTM Standard E 2018-08 for Property Condition Assessments
HOME INSPECTION EDUCATION COURESES (Canada)
HOME INSPECTION EDUCATION COURSES (USA) including home study & live classes at eleven colleges & universities.
HOME INSPECTION EDUCATION: HOME STUDY COURSES - ASHI@Home Training 10-course program.
Special Offer: Carson Dunlop Associates offers InspectAPedia readers in the U.S.A. a 5% discount on these courses: Enter INSPECTAHITP in the order payment page 'Promo/Redemption' space. InspectAPedia.com editor Daniel Friedman is a contributing author. - The Horizon Software System manages business operations,scheduling, & inspection report writing using Carson Dunlop's knowledge base & color images. The Horizon system runs on always-available cloud-based software for office computers, laptops, tablets, iPad, Android, & other smartphones
Descriptions of the ICC diagnostic codes are provided below:
Display Codes | Diagnostic Description | Possible Cause |
---|---|---|
0- Standby | No command for unit operation | Normal operation |
c - First Stage Cooling | Unit has received a command for first stage cooling | Normal operation |
c Flashing | Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active | |
C - Second Stage Cooling | Unit has received a command for second stage cooling | Normal operation |
C Flashing | Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active | |
h - First Stage Heat Pump | Unit has received a command for first stage heat pump | Normal operation |
h Flashing | Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) action | |
H - Second Stage Heat Pum | Unit has received a command for second stage heat pump | Normal operation |
H Flashing | Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active | |
d - Defrost Active | The unit is undergoing a defrost cycle | Normal operation |
t - Test Mod | Test Mod | The ICC is in TEST mode |
P - Protector Trip | A command for compressor operation is present but no current is measured to the compressor | Motor protector open |
01 - Long Run Time (Compressor) | The compressor has continuously run for more than 18 hours in the cooling mode. | |
02 - High Pressure | Compressor limit has opened four (4) times within a call for operation | |
03 - Short Cycling | ICC detects the run time for the past four (4) compressor or cycles is less than three (3) minutes each | |
L4 - Locked Rotor | The ICC detects four (4) consecutive protector trips have occurred and the average run time for each trip is less than 15 seconds | |
05 - Open circuit (Compressor Will not Run) | The ICC has had a protector trip for longer than 4 hours | |
06 - Compressor Open Start Circuit | The ICC detects current in the Run circuit but not in the Start circuit of the compressor | |
L6 - Compressor Open Start Circuit | The ICC detects current in the Run circuit but not in the Start circuit of the compressor four (4) times in one compressor call | |
07 - Compressor Open Run Circuit | The ICC detects current in the Start circuit but not in the Run circuit of the compressor | |
L7 - Compressor Open Run Circuit | The ICC detects current in the Start circuit but not in the Run circuit of the compressor four (4) times in one compressor call | |
09 - Low Secondary Volts | The secondary voltage at R and C is below 18VAC | |
21 - Low Pressure Control Open | The ICC detects the LPC is open. Note: The low pressure control is ignored for the first 90 seconds of compressor operation | |
L21 Flashing | Active Protection, Low Pressure Control Trip | LPC has opened 3 times in the same cooling operation, the ICC has locked out the compressor to protect it. ICC alternately flashes L and 21. |
27 | Low Line Voltage or No Line Voltage Fault | |
28 | High Line Voltage Fault | Check line voltage |
29 | High Pressure Control Open. The ICC detects the HPC is open | |
L29 Flashing - Active Protection | High Pressure Control Trip | LPC has opened 3 times in the same cooling operation, the ICC has locked out the compressor to protect it. ICC alternately flashes L and 29 |
30 - Fuse Open | The ICC detects the on—board fuse is open | |
80 - Low Air Flow | The ICC detects that the indoor unit is not providing the minimum airflow requirements. | Misappliedwrong indoor air mover - replace With properly sized unit. |
83 - Condenser Coil Temperature Fault | The sensor detects an abnormally low or high coil temperature | |
84 - Outdoor Ambient Temperature Fault | The sensor detects an abnormally low or high outdoor ambient temperature | |
93 - Internal Control Fault | The control is not functioning properly. | |
d1 | N0 Shared Data | Replace memory card With correct system information. |
d3 - Airflow CFM Mismatch | The indoor air mover (air handler/furnace) cannot supply the required airflow for proper system operation | Misappliedwrong indoor air mover-replace With properly sized air handler/furnace. |
d4 - (Device) Memory Card Invalid for Device | The data in the memory card inserted into the control board does not match the data in the control. | |
d8 - Old Shared Data | System data is obsolete | If system Will not operate, order new memory card to update system information. |
Rheem AC ICC Diagnostic Codes
Descriptions of the ICC diagnostic codes are provided below: NOTE: Codes must be read from correct side to avoid an error in reading codes.
Electrical Checks Flowchart
Thermostat Call For Cooling, No Cooling
Troubleshooting
Disconnect all power to unit before servicing. Contactor may break only one side. Failure to shut off power can cause electrical shock resulting in personal injury or death.
SYMPTOM: Unit will not run
POSSIBLE CAUSE:
- Power off or loose electrical connection
- Thermostat out of calibration – set too high
- Defective control board
- Blown fuses/tripped breaker
- Transformer defective
- High-pressure control open/Low-pressure control open
- Miswiring of communications
REMEDY:
- Check for correct voltage at line voltage connections in condensing unit.
- Reset.
- Check control board diagnostic codes.
- Replace fuses/reset breaker.
- Check wiring. Replace transformer.
- Reset. Also see high head pressure remedy. The highpressure control opens at 610 PSIG.
- Check communication wiring
SYMPTOM: Outdoor fan runs, compressor doesn’t
POSSIBLE CAUSE:
- Run or start capacitor defective
- Contactor defective
- Loose connection
- Compressor stuck, grounded or open motor winding, open internal overload.
- Low-voltage condition
REMEDY:
- Replace.
- Replace.
- Check for correct voltage at compressor. Check and tighten all connections.
- Wait at least 3 hours for overload to reset. If still open, replace the compressor.
- Add start kit components.
SYMPTOM: Insufficient cooling
POSSIBLE CAUSE:
- Improperly sized unit
- Improper indoor airflow
- Incorrect refrigerant charge
- Air, noncondensibles, or moisture in system
- Bad ID TXV
REMEDY:
- Recalculate load.
- Check. Should be approximately 400 CFM per ton.
- Charge per procedure attached to unit service panel.
- Recover refrigerant. Evacuate and recharge. Add filter drier.
- Replace TXV
SYMPTOM: Compressor short cycles
POSSIBLE CAUSE:
- Incorrect voltage
- Defective overload protector
- Refrigerant undercharge
REMEDY:
- At compressor terminals, voltage must be ± 10% of nameplate marking when unit is operating.
- Replace. Check for correct voltage.
- Add refrigerant.
SYMPTOM: Registers sweat
POSSIBLE CAUSE: Low indoor airflow
REMEDY: Increase speed of blower or reduce restriction. Replace air filter
SYMPTOM: High head, low vapor pressures
POSSIBLE CAUSE:
- Restriction in liquid line, expansion device, or filter drier
- Bad TXV
REMEDY:
- Remove or replace defective component.
- Replace TXV
SYMPTOM: High head, high or normal vapor pressure – Cooling mode
POSSIBLE CAUSE:
- Dirty outdoor coil
- Refrigerant overcharge
- Outdoor fan not running
- Air or noncondensibles in system
REMEDY:
- Clean coil.
- Correct system charge.
- Repair or replace.
- Recover refrigerant. Evacuate and recharge
SYMPTOM: Low head, high vapor pressures
Rheem Furnace Troubleshooting Codes
POSSIBLE CAUSE:
- Bad TXV
- Bad compressor
REMEDY:
- Replace TXV.
- Replace compressor
SYMPTOM: Low vapor, cool compressor, iced indoor coil
POSSIBLE CAUSE:
Rheem Furnace Code 57
- Low indoor airflow
- Operating below 65°F outdoors
- Moisture in system
- Closed ID circuit
REMEDY:
- Increase speed of blower or reduce restriction. Replace air filter.
- Add Low Ambient Kit.
- Recover refrigerant. Evacuate and recharge. Add filter drier.
- Repair or replace ID coil
SYMPTOM: High vapor pressure
POSSIBLE CAUSE:
- Excessive load
- Defective compressor
REMEDY:
- Recheck load calculation.
- Replace.
SYMPTOM: Fluctuating head and vapor pressures
POSSIBLE CAUSE:
- TXV hunting
- Air or noncondensibles in system
REMEDY:
- Check TXV bulb clamp. Check air distribution on coil. Replace TXV.
- Recover refrigerant. Evacuate and recharge.
SYMPTOM: Gurgle or pulsing noise at expansion device or liquid line
Ruud Furnace Code 57
POSSIBLE CAUSE: Air or noncondensibles in system
REMEDY: Recover refrigerant. Evacuate and recharge.
Service Analyzer Charts
Rheem Furnace Diagnostic Codes